CVE-2017-14471 is a vulnerability of currently unknown severity. An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. EPSS estimates a 37.32% chance of exploitation in the next 30 days.

Description

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.

Metrics

EPSS Probability
37.32%

98.3th percentile

Probability of exploitation in the next 30 days. Learn more

Affected Software

VendorProductVersions
RockwellautomationMicrologix 1400 B Firmware<= 21.2

References

Timeline

Published
Last Modified
Status
Modified

Frequently Asked Questions

What is CVE-2017-14471?
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.
How severe is CVE-2017-14471?
Severity scoring for CVE-2017-14471 is pending analysis. The EPSS model estimates a 37.32% probability of exploitation in the next 30 days.
How do I fix CVE-2017-14471?
Check the vendor references and advisories linked above for patched versions and mitigation guidance. You can also run a Strix scan to test if your systems are affected.