CVE-2021-20827

HIGHCVSS 7.5/10EPSS 0.59%

Last modified

CVE-2021-20827 is a high-severity vulnerability rated 7.5/10 on the CVSS scale. Plaintext storage of a password vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from file servers, backup repositories, or ZLD files saved in SD cards. As a result, the attacker may access the PLC Web server and hijack the PLC, and manipulation of the PLC output and/or suspension of the PLC may be conducted.. EPSS estimates a 0.59% chance of exploitation in the next 30 days.

Description

Plaintext storage of a password vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from file servers, backup repositories, or ZLD files saved in SD cards. As a result, the attacker may access the PLC Web server and hijack the PLC, and manipulation of the PLC output and/or suspension of the PLC may be conducted.

Metrics

CVSS 3.1
7.5/10

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

EPSS Probability
0.59%

43.6th percentile

Probability of exploitation in the next 30 days. Learn more

Weakness Enumeration

Affected Software

VendorProductVersions
IdecMicrosmart Fc6a Firmware<= 2.32
IdecMicrosmart Plus Fc6a Firmware<= 1.91
IdecData File Manager<= 2.12.1
IdecWindedit<= 1.3.1
IdecWindldr<= 8.19.1

References

Timeline

Published
Last Modified
Status
Modified

Frequently Asked Questions

What is CVE-2021-20827?
Plaintext storage of a password vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from file servers, backup repositories, or ZLD files saved in SD cards. As a result, the attacker may access the PLC Web server and hijack the PLC, and manipulation of the PLC output and/or suspension of the PLC may be conducted.
How severe is CVE-2021-20827?
CVE-2021-20827 has a CVSS score of 7.5/10 (HIGH severity). The EPSS model estimates a 0.59% probability of exploitation in the next 30 days.