CVE-2026-3611

CRITICALCVSS 10/10EPSS 5.58%

Last modified

CVE-2026-3611 is a critical-severity vulnerability rated 10/10 on the CVSS scale. The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. EPSS estimates a 5.58% chance of exploitation in the next 30 days.

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Metrics

CVSS 3.1
10/10

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

CVSS 4.0
10/10

CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

EPSS Probability
5.58%

91.9th percentile

Probability of exploitation in the next 30 days. Learn more

Weakness Enumeration

Affected Software

VendorProductVersions
HoneywellIq4e Firmware< 3.30
HoneywellIq412 Firmware< 3.30
HoneywellIq422 Firmware< 3.30
HoneywellIq4nc Firmware< 3.30
HoneywellIq41x Firmware< 3.30

References

Timeline

Published
Last Modified
Status
Analyzed

Frequently Asked Questions

What is CVE-2026-3611?
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
How severe is CVE-2026-3611?
CVE-2026-3611 has a CVSS score of 10/10 (CRITICAL severity). The EPSS model estimates a 5.58% probability of exploitation in the next 30 days.
How do I fix CVE-2026-3611?
Check the vendor references and advisories linked above for patched versions and mitigation guidance. You can also run a Strix scan to test if your systems are affected.

Are you affected by CVE-2026-3611?

Run a free Strix scan to check your systems for this vulnerability.

Scan your code now

Source: NVD / NIST