CVE-2026-46674

HIGHCVSS 7.5/10

Last modified

CVE-2026-46674 is a high-severity vulnerability rated 7.5/10 on the CVSS scale. BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to versions 1.4.4 and 1.5.1, an out-of-bounds read vulnerability exists in bacnet-stack's AtomicWriteFile record-access path.

Description

BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to versions 1.4.4 and 1.5.1, an out-of-bounds read vulnerability exists in bacnet-stack's AtomicWriteFile record-access path. The bug is caused by a mismatch between an externally controlled returnedRecordCount field and the fixed-size internal fileData[] array used by BACNET_ATOMIC_WRITE_FILE_DATA. This issue has been patched in versions 1.4.4 and 1.5.1.

Metrics

Weakness Enumeration

Affected Software

Source: CNA advisory (CVE.org). NVD analysis pending.

VendorProductVersions
bacnet-stackbacnet-stack< 1.4.4; < 1.5.1

References

Timeline

Published
Last Modified
Status
Awaiting Analysis

Frequently Asked Questions

What is CVE-2026-46674?
BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to versions 1.4.4 and 1.5.1, an out-of-bounds read vulnerability exists in bacnet-stack's AtomicWriteFile record-access path. The bug is caused by a mismatch between an externally controlled returnedRecordCount field and the fixed-size internal fileData[] array used by BACNET_ATOMIC_WRITE_FILE_DATA. This issue has been patched in versions 1.4.4 and 1.5.1.
How severe is CVE-2026-46674?
CVE-2026-46674 has a CVSS score of 7.5/10 (HIGH severity).