CVE-2022-30316

MEDIUMCVSS 6.8/10EPSS 0.34%

Last modified

CVE-2022-30316 is a medium-severity vulnerability rated 6.8/10 on the CVSS scale. Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. EPSS estimates a 0.34% chance of exploitation in the next 30 days.

Description

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.

Metrics

CVSS 3.1
6.8/10

CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

EPSS Probability
0.34%

26.3th percentile

Probability of exploitation in the next 30 days. Learn more

Weakness Enumeration

Affected Software

VendorProductVersions
HoneywellSafety Manager FirmwareAll versions

References

Timeline

Published
Last Modified
Status
Modified

Frequently Asked Questions

What is CVE-2022-30316?
Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.
How severe is CVE-2022-30316?
CVE-2022-30316 has a CVSS score of 6.8/10 (MEDIUM severity). The EPSS model estimates a 0.34% probability of exploitation in the next 30 days.
How do I fix CVE-2022-30316?
Check the vendor references and advisories linked above for patched versions and mitigation guidance. You can also run a Strix scan to test if your systems are affected.

Are you affected by CVE-2022-30316?

Run a free Strix scan to check your systems for this vulnerability.

Scan your code now