CVE-2022-30320

MEDIUMCVSS 4.3/10EPSS 0.23%

Last modified

CVE-2022-30320 is a medium-severity vulnerability rated 4.3/10 on the CVSS scale. Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. EPSS estimates a 0.23% chance of exploitation in the next 30 days.

Description

Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.

Metrics

CVSS 3.1
4.3/10

CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N

EPSS Probability
0.23%

13.6th percentile

Probability of exploitation in the next 30 days. Learn more

Weakness Enumeration

Affected Software

VendorProductVersions
HoneywellSaia Pg5 Controls SuiteAll versions

References

Timeline

Published
Last Modified
Status
Modified

Frequently Asked Questions

What is CVE-2022-30320?
Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
How severe is CVE-2022-30320?
CVE-2022-30320 has a CVSS score of 4.3/10 (MEDIUM severity). The EPSS model estimates a 0.23% probability of exploitation in the next 30 days.
How do I fix CVE-2022-30320?
Check the vendor references and advisories linked above for patched versions and mitigation guidance. You can also run a Strix scan to test if your systems are affected.

Are you affected by CVE-2022-30320?

Run a free Strix scan to check your systems for this vulnerability.

Scan your code now

Source: NVD / NIST